HORNBILL 1000S & 2000S

Hornbill Static switch have different user selectable parameters with DSP control. It is excellent performance enhancement system useful for Data center, Process Automation, Power plant, Healthcare, Telecom, Broadcasting, Industry type of environment.

TECHNICAL SPECIFICATIONS

MODEL Hornbill 1000s Hornbill 2000s
INPUT / OUTPUT
Nominal Voltage 110 / 115/230 / 240 VAC (1 Ph + N)
Voltage Tolerances +/- 15%
Frequency Tolerances wide band 40 - 70 Hz Auto Selectable
Power Capacity 16A / 32A
No. of Switching Poles SINGLE TWO
Overload Capacity 110% for 1 hour, 150% for 60 s, 200% for 10 s, 1000% for 100 ms
Duty Continuous
Load Power Factor range 0.2 to unity leading or lagging
Source Voltage Distortion > 10% THD
Controller 32 bit DSP
SWITCH
Transfer < 5 ms in sync & No sync
Retransfer < 5 ms in sync & No sync
Manual Bypass Provided
Efficiency (Ref. IEC 60146-1-1)* ≥ 99% ≥ 98%
ENVIRONMENTAL
Operating Temperature 0 to 40° C
Storage Temperature 0 to 70° C
Relative Humidity up to 95% (Non-condensing)
Acoustic Noise @ 1m (Ref. ISO 3746) ≤ 45 dBA
Altitude
PHYSICAL
Enclosure Protection IP – 20
Cooling Natural
Color RAL 7016
Cable Entry Back
Dimensions 3 U (485 x 450 x 132 mm)
Installation 19” Rack Mountable
USER INTERFACE
Indications Source 1 Healthy, Source 1 Priority, Source 1 Feeding, Source 1 Manual bypass ON, Output ON
Source 2 Healthy, Source 2 Priority, Source 2 Feeding, Source 2 Manual bypass ON, No Sync
Fault Indication Overload
Standards IEC 62310-1, IEEE 446
Other Features RS 485 MODBUS
Specifications are subject to change without prior notice due to constant improvement in design & technology
Custom models available on request